Ungrounded voltage transformers NOLP (НОЛП) with build-in ptotection deviceUngrounded voltage transformers NOLP (НОЛП) with build-in ptotection device
Description
The transformers are intended for embedding in factory-assembled switchgears and conductors and are used for powering electrical protection, signaling and control circuits of alternating current electrical systems with 50 or 60 Hz frequency.
The transformers are manufactured in climatic versions "У" (moderate) and "T" (tropical) according to the standard requirements of GOST 15150 location category 2 with built-in protection device.
Mounting in any position.
The transformer is patented Patent Certificate № 2208860 Patent certificate № 53160 on industrial unit.
Table 1. Technical data
Parameter
|
Normal value
|
Electro-magnetic portion (transformer)
|
Built-in protection device
|
Voltage class, kV
|
6
|
10
|
10
|
Maximum working voltage, kV
|
7,2
|
12
|
12
|
Rated voltage of the primary winding, V
|
6000 6300 6600 6900
|
10000 11000
|
-
|
Rated voltage of the secondary winding, V
|
100 or 110*
|
-
|
Rated power of the main secondary winding, VA in accuracy class**: 0,2*** 0,5 1 3
|
30 50 75 200
|
50 75 150 300
|
-
|
Maximum power out of accuracy class, VA
|
400
|
630
|
-
|
Test voltage, kV: one-minute of industrial frequency of full lighting impulse of cut lighting impulse
|
32 60 70
|
42 75 90
|
-
|
Rated frequency, Hz
|
50 or 60
|
-
|
Resistance of resistor in the protection device, Ohm
|
-
|
36/18
|
Resistor rated power, W
|
-
|
0,25/0,125
|
Vector group of transformer
|
1/1-0
|
-
|
Notes: Transformers for Automated Systems of Commercial Calculations of Electrical Energy are supplied at the special order with single accuracy class and rated power specified in the order.
*) Rated voltage of secondary winding of 110 V, only for transformers with rated voltage of primary winding of 6600 and 11000V. **) Highest accuracy class should be specified in the order. ***) Highest accuracy class of 0,2 is only available for transformers with rated voltage of secondary winding of 100 V.
General view of transformer (drawing)
|