One-phase distribution transformers OL (ОЛ) on powers of 0,63 and 1,25 kVAOne-phase distribution transformers OL (ОЛ) on powers of 0,63 and 1,25 kVA
Description
The transformers are intended for powering automatic block-system of railway longitudinal electric powering. The transformer is manufactured in climatic version "УХЛ" (moderate cold) and "T" (tropical) of the location category 1 to ГОСТ 15150 and is intended for operation in outside at the following conditions:
- ambient air temperature at operation is from minus 60 to plus 50°C;
- the upper value of air humidity is 100% at 25 °C for "УХЛ1" version;
- ambient air temperature at operation is from minus 10 to plus 55°C for "T1" version;
- the upper value of air humidity is 100% at 35 °C for "T1" version;
- creepage distance - III according to GOST 9920-89;
- two transformers with equal rated voltage of the primary winding and common rated capacity value may operate in parallel;
- mounting in any position
Design
The transformer is one-phase and with two windings. The axial-type core tape-type is wound of cold-rolled electro technical steel. Windings are located concentrically on the core. Secondary winding terminals are connected to the contacts by means of thread.
The transformer is patented Patent publications No 2087967, 2110862, 2193252, Patent Certificates on industrial unit No 42733.
Table 1. Technical data
Parameter
|
Normal values
|
OL-0,63/6
|
OL-1,25/6
|
OL-0,63/10
|
OL-1,25/10
|
Voltage class, kV
|
6
|
10
|
Maximum operating voltage, kV
|
7,2
|
12
|
Rated voltage of the primary winding, kV
|
6,3
|
10,5
|
Rated voltage of the secondary winding*, V:
|
.
|
х-а1
|
218
|
х-а2
|
224
|
х-а3
|
230
|
х-а4
|
236
|
x-a5
|
242
|
Rated frequency, Hz
|
50 or 60
|
Rated power at the rated voltages 100 and 220V, VA
|
630
|
1250
|
630
|
1250
|
No-load current, %, not more
|
70
|
35
|
70
|
35
|
No-load current losses, Wt, not more
|
50
|
Short circuit voltage,%
|
4,5
|
Short circuit losses, Wt, not more
|
55
|
Test voltage, Hz of industrial frequency during one minute of full lighting impulse of cut lighting impulse
|
25 60 70
|
25 60 70
|
Vector group of transformer
|
1/1-0
|
Mass, kg:
|
40
|
42
|
General view of transformer (drawing)
|