Distribution transformer OLSPDescription

The transformers are intended for embedding in factory-assembled switchgears, conductions and are used for powering measuring, protection, signal and control circuits in electrical devices of alternating current with frequency 50 or 60 Hz. Transformers are manufactured in compliance with the standard requirements of GOST 15150 in climatic versions "Y" (temperate) and "T" (tropical) location category 2.

Mounting in any position.

The transformer is patented
1. Patent certificate № 2208860.
2. Certificate № 53160 on industrial unit. 

Table 1. Technical data

Parameter

Normal value

OLSP-0,63/6

OLSP-0 ,63/10

OLSP-1,25/6

OLSP-1,25/10

Voltage class, kV

6

10

6

10

Maximum operating voltage, kV

7,2

12

7,2

12

Rated voltage of the primary winding, kV

6,3; 6,6

10,5; 11

6,3; 6,6

10,5; 11

Rated voltage of the secondary winding*, V:
а1 - х
а2 - х
а3 - х
а4 - х

100
209
220
231

Rated power at rated voltage of 100 and 220 V, VA

630

1250

Vector group of transformer

1/1-0

Rated frequency, Hz

50 or 60

Test voltage, kV:
one-minute of industrial frequency
of full lighting impulse
of cut lighting impulse


25
60
70


35
75
90


25
60
70


35
75
90

Resistance of the safeguard resistor, Ohm

18

36/18

6

13

Rated power of resistor, Wt

0,25

0,25/0,125

0,25

General view of transformer (drawing)