Description
The transformers are intended for embedding in factory-assembled switchgears, conductions and are used for powering measuring, protection, signal and control circuits in electrical devices of alternating current with frequency 50 or 60 Hz. Transformers are manufactured in compliance with the standard requirements of GOST 15150 in climatic versions "Y" (temperate) and "T" (tropical) location category 2.
Mounting in any position.
The transformer is patented 1. Patent certificate № 2208860. 2. Certificate № 53160 on industrial unit.
Table 1. Technical data
Parameter
|
Normal value
|
OLSP-0,63/6
|
OLSP-0 ,63/10
|
OLSP-1,25/6
|
OLSP-1,25/10
|
Voltage class, kV
|
6
|
10
|
6
|
10
|
Maximum operating voltage, kV
|
7,2
|
12
|
7,2
|
12
|
Rated voltage of the primary winding, kV
|
6,3; 6,6
|
10,5; 11
|
6,3; 6,6
|
10,5; 11
|
Rated voltage of the secondary winding*, V: а1 - х а2 - х а3 - х а4 - х
|
100 209 220 231
|
Rated power at rated voltage of 100 and 220 V, VA
|
630
|
1250
|
Vector group of transformer
|
1/1-0
|
Rated frequency, Hz
|
50 or 60
|
Test voltage, kV: one-minute of industrial frequency of full lighting impulse of cut lighting impulse
|
25 60 70
|
35 75 90
|
25 60 70
|
35 75 90
|
Resistance of the safeguard resistor, Ohm
|
18
|
36/18
|
6
|
13
|
Rated power of resistor, Wt
|
0,25
|
0,25/0,125
|
0,25
|
General view of transformer (drawing)
|