- Current transformers
- Voltage transformers
- Distribution transformers
- Three-phase distribution transformer ТЛС (TLS) with cast resin insulation
- One-phase distribution transformers OL (ОЛ) on powers of 0,63 and 1,25 kVA
- One-phase distribution transformers OL (ОЛ) on powers of 2,5 and 4 kVA
- One-phase distribution transformers OL-6,3
- One-phase distribution transformers OLS (ОЛС) on powers of 0,63 and 1,25 kVA
- One-phase distribution transformers OLS (ОЛС) on powers of 2,5 and 4 kVA
- One-phase distribution transformers OLS-6,3
- Distribution transformers OS (ОС)
- Adapter transformers OL-1/10 (ОЛ-1/10)
- Distribution transformers OLSP (ОЛСП) with built-in protctive device
- Distribution transformers OLZ-1,25/27,5 (ОЛЗ-1,25/27,5)
- Network decoupling transformers OL-0,3/35 (ОЛ-0,3/35)
- Zero-phase sequence transformers
|
Three-phase distribution transformer ТЛС (TLS) with cast resin insulationThree-phase distribution transformer TLS with cast resin insulation
Description
The transformers of TLS series (according to GOST 11677) are manufactured to satisfy needs of power industry, particullarly needs of power objects. Transformers are manufactured in 6 or 10 kV voltage classes according to standard requirmets of GOST 15150 in climatic version "YHL" (temperate outside mounting) location category 2 and are intended for usage under the following operating conditions:
- altitude above sea level is not higher then 1000 m;
- ambient air temperature considering overheating inside factorey-assembled switchgear from minus 50°С up to plus 50°С;
- relative humidity not higher than 100% at 25°С;
- environment should be non-explosive, without corrosive steams in concentrations that are likely to destroy metal or insulation (atmosphere type II as to GOST 15150);
- mounting in vertical position.
The transformers are intended for usage in electrical appliances which are subject to lighting overvoltage at standard safety requirements, and have standard "b" level insulation as to GOST 1516.3, thermal stability class "B" as to GOST 8865 and inflammability class FH I as to GOST 28779.
Table 1. Technical data of distribution transformers TLS of powers 10-63 kVA
Parameter
|
TLS-10
|
TLS-16
|
TLS-25
|
TLS-40
|
TLS-63
|
Power rating, kVA
|
10
|
16
|
25
|
40
|
63
|
Rated frequency, Hz
|
50
|
50
|
50
|
50
|
50
|
Voltage HV, kV
|
6; 6,3; 10; 10,5
|
Voltage LV, V
|
400
|
400
|
400
|
400
|
400
|
Vector group of transformer
|
D/Yn-11; Y/Yn-0
|
D/Yn-11; Y/Yn-0; Y/Zn-11
|
Short circuit voltage, %
|
4,4
|
3,3
|
2,8
|
2,7
|
2,1
|
Short circuit losses, Wt
|
280
|
320
|
470
|
650
|
800
|
No-load current, %
|
4,9
|
4,8
|
2,0
|
1,8
|
1,5
|
No-load losses, Wt
|
95
|
135
|
150
|
200
|
350
|
Mass, kg.
|
150
|
180
|
240
|
270
|
500
|
Note. Transformers may be manufactured with different vector groups and parameters.
Table 2. Dimensions of transformers TLS on powers 10 and 16 kVA
Transformer type
|
Dimensions, mm
|
Weight, kg
|
A
|
B
|
C
|
D
|
E
|
F
|
TLS-10
|
557
|
510
|
38
|
115
|
155
|
128
|
150
|
TLS-16
|
577
|
530
|
48
|
125
|
165
|
146
|
180
|
Table 3. Dimensions of transformers TLS on powers 25, 40 and 63 kVA
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H
|
I
|
J
|
K
|
L
|
TLS-25
|
656
|
296
|
758
|
730
|
300
|
480
|
222
|
410
|
170
|
225
|
263
|
170
|
TLS-40
|
656
|
320
|
775
|
755
|
300
|
480
|
222
|
400
|
182
|
225
|
270
|
192
|
TLS-63
|
745
|
407
|
820
|
805
|
400
|
625
|
255
|
390
|
210
|
325
|
245
|
192
|
Table 4. Technical data of distribution transformer TLS on powers 100-2500 kVA
Parameter
|
Value
|
Power, kVA
|
100-2500
|
Vector group of transformer
|
D/YH-11, Y/YH-0
|
Material of HV and LV windings
|
copper
|
Rated HV voltage, kV
|
(6,10)+/-2х2,5%
|
Rated LV voltage, V
|
400
|
Thermal stability level
|
F (155oC)
|
Climatic version
|
УХЛ2 (moderate)
|
Protection level
|
IP00, IP21, IP31
|
Lifetime
|
25 years
|
Warranty period
|
3 years
|
Standard
|
GOST P52719, GOST 11677
|
Table 5.
Power ratings, kVA
|
Uh1, кВ
|
Losses, Wt
|
No load current, Io, %
|
Usc, %
|
Weight, kg
|
Ро
|
Рs.c.(115°С)
|
100
|
6 or 10
|
390
|
1620
|
0,8
|
6
|
670
|
160
|
6 or 10
|
550
|
2300
|
0,6
|
6
|
930
|
250
|
6 or 10
|
800
|
3220
|
0,6
|
6
|
1330
|
400
|
6 or 10
|
1050
|
4780
|
0,6
|
6
|
1750
|
630
|
6 or 10
|
1420
|
5300
|
0,4
|
6
|
2450
|
1000
|
6 or 10
|
1750
|
7600
|
0,3
|
6
|
3300
|
1250
|
6 or 10
|
2300
|
10500
|
0,3
|
6
|
3600
|
1600
|
6 or 10
|
2600
|
14000
|
0,3
|
6
|
4700
|
2500
|
6 or 10
|
4000
|
15500
|
0,3
|
6
|
6500
|
Table 6. Dimensions of distribution transformers TLS on power 100-2500 kVA
Power ratings, kVA
|
100
|
160
|
250
|
400
|
630
|
1000
|
1250
|
1600
|
2500
|
L, mm
|
1080
|
1280
|
1380
|
1470
|
1600
|
1630
|
1700
|
1820
|
2060
|
L1, mm
|
370
|
435
|
470
|
500
|
535
|
545
|
570
|
590
|
700
|
L2, mm
|
930
|
1070
|
1150
|
1380
|
1400
|
1430
|
1580
|
1700
|
1940
|
H, mm
|
1010
|
1150
|
1290
|
1370
|
1445
|
1685
|
2070
|
2090
|
2430
|
H1, mm
|
945
|
1085
|
1220
|
1315
|
1422
|
1645
|
2010
|
2020
|
2365
|
H2, mm
|
690
|
815
|
905
|
908
|
945
|
1200
|
1425
|
1430
|
1675
|
H3, mm
|
330
|
355
|
375
|
399
|
455
|
460
|
535
|
575
|
575
|
B, mm
|
600
|
600
|
600
|
700
|
970
|
970
|
970
|
970
|
1250
|
B1, mm
|
500
|
500
|
500
|
600
|
820
|
820
|
820
|
820
|
1070
|
B2, mm
|
445
|
530
|
520
|
530
|
650
|
650
|
650
|
650
|
750
|
Dimensions of connecting busbars LV, pic.
|
1
|
1
|
1
|
2
|
3
|
3
|
3
|
3
|
3
|
K, mm
|
30
|
30
|
40
|
60
|
80
|
80
|
30
|
30
|
30
|
M, mm
|
15
|
15
|
20
|
15
|
17,5
|
17,5
|
25
|
25
|
30
|
N, mm
|
-
|
-
|
-
|
30
|
45
|
45
|
50
|
50
|
60
|
D, mm
|
11
|
11
|
13
|
11
|
13
|
13
|
17
|
17
|
17
|
General view of transformer (drawing; 10 and 16 kVA)
General view of transformer (drawing; 25, 40 and 63 kVA)
General view of transformer (drawing; 100-2500 kVA)
Distribution transformer TLS in protective cover

Table 7. Dimensions of protective cover for distribution transformers TLS on powers 10-63 kVA
Transformer type
|
Dimensions, mm
|
Weight, kg
|
H
|
H1
|
L
|
L1
|
L2
|
B
|
B1
|
B2
|
B3
|
TLSZ-10(16)
|
800
|
640
|
930
|
470
|
400
|
670
|
505
|
415
|
110
|
210 (245)
|
TLSZ-25
|
1140
|
970
|
950
|
520
|
480
|
735
|
645
|
600
|
130
|
320
|
TLSZ-40
|
520
|
145
|
380
|
TLSZ-63
|
625
|
175
|
530
|
General view of protective cover (drawing; 10-63 kVA)
Table 8. Dimensions of protective cover for distribution transformers TLS on powers 100-2500 kVA
Power, kVA
|
Dimensions, mm
|
100
|
160 |
250
|
400
|
630
|
1000
|
1250
|
1600
|
2500 |
H
|
1280
|
1405 |
1565
|
1610
|
1810
|
2110
|
2370
|
2535
|
2840 |
H1
|
1220
|
1345 |
1515
|
1555
|
1715
|
2015
|
2300
|
2460
|
2780 |
H2
|
920
|
1040 |
1405
|
1245
|
1395
|
1685
|
1800
|
1965
|
2315 |
B
|
1025
|
1055 |
1100
|
1130
|
1150
|
1185
|
1150
|
1580
|
1780 |
B1
|
500
|
500 |
600
|
600
|
600
|
820
|
820
|
820
|
1070 |
B2 |
110 |
110 |
150 |
150 |
150 |
150 |
150 |
180 |
180 |
L
|
1725
|
1875 |
2105
|
2205
|
2240
|
2285
|
2380
|
2735
|
2985 |
L1 |
1600 |
1750 |
1940 |
2020 |
2055 |
2075 |
2160 |
2500 |
2760 |
L2 |
220 |
220 |
260 |
260 |
260 |
300 |
300 |
350 |
350 |
L3 |
105 |
105 |
115 |
115 |
130 |
130 |
130 |
192 |
192 |
L4 |
160 |
105 |
115 |
120 |
120 |
135 |
135 |
192 |
192 |
L5 |
160 |
160 |
170 |
170 |
190 |
205 |
205 |
275 |
275 |
k
|
30
|
30 |
40
|
60
|
80
|
80
|
100
|
100
|
120 |
N
|
-
|
- |
-
|
15
|
45
|
45
|
50
|
50
|
60 |
M
|
15
|
15 |
20
|
17,5
|
17,5
|
17,5
|
17,5
|
25
|
30 |
h
|
60
|
60 |
70
|
90
|
90
|
110
|
130
|
130
|
130 |
D
|
13
|
13 |
13
|
11
|
13
|
13
|
13
|
17
|
17 |
S*
|
3
|
3 |
4
|
4
|
5
|
8
|
8
|
10
|
15 |
Variation
|
2
|
2 |
2
|
1
|
1
|
1
|
1
|
1
|
1 |
Weight, kg
|
880
|
1150 |
1590
|
2065
|
2790
|
3700
|
4500
|
5330
|
7200 |
* S - thicknes of HV bus-bar; dimensions of LV bus-bar = 40x5mm